Paramete |
Function |
Set range |
Default |
E1 |
Lower setpoint limit |
-45ºC~Set temp. |
-30ºC |
E2 |
Higher setpoint limit |
Set temp.~50ºC |
30ºC |
E3 |
Temp.hysteresis |
1~10ºC |
4ºC |
E4 |
Comp.start delay time |
0~10Min |
2Min |
E5 |
Offset on room temp. |
-10~10ºC |
0 |
E6 |
Offset on evap.temp. |
-10~10ºC |
0 |
F0 |
Defrost function |
0=Electric heater 1=Hot gas |
0 |
F1 |
Max.Defrost duration |
1~60Min |
20Min |
F2 |
Defrost interval time |
0~24Hr |
6Hr |
F3 |
Defrost termination temp. |
0~50~0ºC |
8ºC |
F4 |
Display during defrost |